+44 (0) 118 9700010 sales@icc-gb.com |
|
|
|
| ESCB Series | | 3 pole Moulded Case Circuit Breaker according to IEC, EN, DIN VDE for control and system protection |
| | Rated operational current Ie = 1000A | |
| | Normal and high short circuit switching capacity with types ESCB1 and ESCB2 | |
| | Rated insulation voltage AC up to 690V, DC up to 440V | |
| | Overload release adjustable 9.4 - 1000A in 20 settings | |
| | Short circuit release adjustable or set tight | |
| | Main switching characteristics according to IEC 204-1; DIN EN 60204-1; VDE 0113 part 1 | |
| | Disconnecting characteristics according to IEC 947-3; DIN VDE 0660 Part 107; EN 60947-3 | |
| | Protection against contact to DIN VDE 0106 part 100 | |
| | Unlimited on-period | |
| | Accessories: undervoltage release, shunt release, auxiliary contact | |
| | Applications for switching
and protection of - Generators - Transformers - Wires - Systems |
|
|
|
|
ESCB1 ESCB1A |
ESCB2 ESCB2A |
ESCB3, ESCB4 |
|
|
|
|
|
|
|
Overall Comparison
| Regulations | IEC 947-2; EN 60947-2; DIN VDE 0660 part 101 |
| General Information | ESCB1 | ESCB1A | ESCB2 | ESCB2A | ESCB3 | ESCB4 | |
| Rated impulse withstand voltage | kV | 6 | 8 | 6 | 8 | 8 | 8 |
| Utilization category | A | A | A | A | A | A | |
| Mechanical lifespan | Ops | 20000 | 20000 | 10000 | 10000 | 10000 | 10000 |
| Electrical lifespan | Ops | 4000 | 4000 | 2000 | 2000 | 4000 | 4000 |
| Ambient temp. min/max | °C | -10/+55 | -10/+55 | -10/+55 | -10/+55 | -10/+55 | -10/+55 |
| Weight | kg | 1.85 | 1.85 | 5.2 | 5.2 | 12.0 | 13.2 |
| Main Poles | |||||||
| Rated continuous current Iu | A | 160 | 160 | 400 | 400 | 630 | 1000 |
| Rated operational voltage Ue - AC | V | 500 | 690 | 690 | 690 | 690 | 690 |
| Rated operational voltage Ue - DC | V | 250 | 250 | 440 | 440 | 440 | 440 |
| Frequency | Hz | 50 - 60 | 50 - 60 | 50 - 60 | 50 - 60 | 50 - 60 | 50 - 60 |
| Protection (front) | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |