Specification
APPLICATION VOLTAGE |
22 Type |
3 Phase 160 ~ 300VAC 50/60Hz |
||
44 Type |
3 Phase 340 ~ 480VAC 50/60Hz |
|||
Reset |
5sec, Auto-Rest : When the input power returns to nomal condition. |
|||
Manual Reset : Depressing Reset Button on relay fascia or interruption of 3 phase input |
||||
TOLERANCE |
Volage |
|
Time |
|
Output contact |
SPDT 3 A/250 VAC Resistive, Normally Energized (OPEN,CLASE) |
|||
Ambient temperature |
Store |
-30 ~ 80 |
Operation |
-20 ~ 70 |
Humidity |
45 ~ 85%RH Without condensation |
|||
Insulation |
Between casing and circuit |
Over 10 |
||
Dielectric strenth |
Between casing and circuit |
2KV 60Hz, 1min. |
||
Between contacts |
1KV 60Hz, 1min. |
|||
Between circuit |
2KV 60Hz, 1min. |
|||
Power consumption |
0.7 Watt. |
|||
Mounting |
DIN Rail(35mm) Mount panel mount |
|||
Function
PROTECTION |
TRIP DELAY |
DESERIPTION |
Phase reversal |
Within 0.1Sec |
When abnormal phase sequence power is supplied. |
Phase loss |
Within 1Sec |
When phase failure occurs. |
Voltage Unbalance |
5 Sec |
2~15% adjustable with protentionmeter. % voltage |
Fail Safe |
When the input power is abnormal-either phase reversal or phase |
|