SPECIFICATION 

MODEL

DCL(Direct Current Limiter)

Current sensing type

Shunt

Hole Sensor

Current Range

10) 1 - 10mV

05) 0.5 - 5A

50) 5 - 50A

70) 0 - 70mV

100) 10 - 100A

200) 20 - 200A

Operating Time

0.2 - 30 seconds

Accuracy

Current

10%

Time

15% at max set value

Time characteristics

Definite Time

Control Voltage

110/220(200 - 240)VAC 50/60Hz, Dual
# 24/48VAC/DC & Other voltage optional

Relay Output

SPDT, 3A/250VAC, 50/60Hz,resistive

Output mode

Relay deenergized in normal state

Expected relay life

Mechanical : 200,000,000 operations

Electrical : 100,000 operations at rated load

Indication

red LED

Reset

Manual or remote electrical reset with control power interruption.
Auto(instant) reset optional

Environment

Temp.

Run

-20 + 60

Store

-30 + 70

Humidity

45 ~ 85% RH, non-condsing

Insulation

Between casing and circuits: over 10 DC500V megger

Dielectric strength

1)Between casing & circuits : AC 2,000V, 60Hz, 1min

2)Between open contacts : AC 1,000V, 60Hz, 1min

Current sensor rating & Hole sensor size(ID)

Shunt

50mV at rated currents

Hole

4V at rated currents, sensor ID 20mm

Mounting

Panel

Weight

approximately 175g less sensor