EOCR-SS2,SS3
MCU Based Motor Protection Relay/Digital Overload Relay

Introduction
1) MCU (Microcontroller Unit) based.
2) Compact design
3) Overcurrent/Phase Loss/Phase Reversal(SS3)/
Locked Rotor Protection
5) Wide adjustment range up to 1 : 10
6) Independently adjustable starting period & Trip delay
7) Visual adjustment aid (LED)
8) Identify cause of trip (2 LED signals)
9) Manual/Electrical reset
10) NVR Funtion(No volt release/Fail-safe Protection)
Setting guide
After completion of wiring, set the values as following instruction :
1. Set starting period to known motor run up time or to the maximum
if not known with D-Time knob.
2. Set trip delay to desired trip delay time with O-TIME knob.
3. Start the motor and notice run-up time. then, slowly turn the LOAD knob
CCW,
until red LED flashes, where the 100% of the actual
load current is indicated.
Set the LOAD knob to desired trip current. 110бн125%
setting of running
current is recommended.
4. Readjust D-TIME knob setting to normal motor run-up time.
5. Periodic testing with TEST button is recommended to ensure the full protection
and regularly as a preventive maintenance.
SS2,SS3 Time-current characteristics

Easy troubleshooting

Opdering information