           EOCR-SS2,SS3

MCU Based Motor Protection Relay/Digital Overload Relay

Introduction

1)   MCU (Microcontroller Unit) based.
2)   Compact design
3)   Overcurrent/Phase Loss/Phase Reversal(SS3)/
      Locked Rotor Protection
5)   Wide adjustment range up to 1 : 10
6)   Independently adjustable starting period & Trip delay
7)   Visual adjustment aid (LED)
8)   Identify cause of trip (2 LED signals)
9)   Manual/Electrical reset
10) NVR Funtion(No volt release/Fail-safe Protection)

Setting guide

After completion of wiring, set the values as following instruction :
1. Set starting period to known motor run up time or to the maximum
    if not known with D-Time knob.
2. Set trip delay to desired trip delay time with O-TIME knob.
3. Start the motor and notice run-up time. then, slowly turn the LOAD knob CCW,
    until red LED flashes, where the 100% of the actual load current is indicated.
    Set the LOAD knob to desired trip current. 110бн125% setting of running
    current is recommended.
4. Readjust D-TIME knob setting to normal motor run-up time.
5. Periodic testing with TEST button is recommended to ensure the full protection
    and regularly as a preventive maintenance.

SS2,SS3 Time-current characteristics

Easy troubleshooting

Opdering information

Dimension

Typical application

Specification, Protection, Visual aid of LEDs