Electronic
Overload Relay-Terminal Type
Definite
Time Type
EOCR-SP

Introduction
1) Compact design
2) Wide adjustment range
3) Visual adjustment aid ( LED )
4) Manual / Electrical reset
5) Fail Safe Protection ( N Type )
Setting guide
After completion of wiring, set the values as following
instruction :
1. Set trip delay to desired trip delay time longer than motor
run-up time with O-TIME knob.
2. Start the motor and notice run-up time. Then, slowly
turn the LOAD knob CCW, until red LED flashes,
where the 100% of the actual load current is indicated.
Set the knob to desired trip current. 110бн125% setting
of running current is recommended.
3. Periodic testing with TEST button is recommended
to ensure the full protection and regularly as
a preventive maintanence.(When the motor stops)