MCU Based Motor Protection Relay/Digital Overload Relay(-Terminal type)

            EOCR - DS1(T)

                       Inverse Time Type

Introduction

1)  MCU (Microprocessor Unit) based.
2)  Compact design
3)  Overcurrent/Phase Loss / Locked Rotor
4)  Protection
5)  Wide adjustment range up to 1 : 10
6)  Independently adjustable starting period & Trip delay
7)  Visual adjustment aid (LED)
8)  Identify cause of trip (2 LED signals)
9)  Manual/Electrical reset
10) Flexible Power Supply

EOCR-DS1 + POWER TERMINAL KIT = EOCR-DS1(T)

Easy troubleshooting

DS1 Time-current characteristics

Setting guide

After completion of wiring, set the values as following
instruction :
1. Set starting period to known motor run up time or to the
    maximum if not known with D-Time knob.
2. Set trip delay to desired trip delay time with O-TIME knob.
3. Start the motor and notice run-up time. then, slowly turn
    the LOAD knob CCW, until red LED flashes, where the
    100% of the actual load current is indicated. Set the LOAD
    knob to desired trip current. 110бн125% setting of running
    current is recommended.
4. Readjust D-TIME knob setting to normal motor run-up time.
5. Periodic testing with TEST button is recommended to ensure
    the full protection and regularly as a preventive maintenance.