             DIGITAL MULTI-FUNCTIONAL PROTECTIVE RELAY
         WITH GROUND FAULT PROTECTION AND AMMETER

                EOCR-3DZ

                                     O.L & Ground Fault protection,
                        Selectable Charactenistic : Definite / Inverse Time

                     

Introduction

BASED ON MCU(Micro Controller Unit) AND ADOPTED
ASIC (Application Specific Intergrated circuit) CHIP.
MULTI FUNCTIONAL PROTECTION - OVERCURRENT,
PHASE REVERSAL, PHASE LOSS, PHASE UNBALACE,
LOCKED ROTOR, GROUND FAULT.
1. The 3phase currents and earth leakage current are
    displayed in sequence.
2. Possible setting with potentiometer.
   (overcurrent, delay time, operating time, ground
    fault current)
3. Selectable functions and CT ratios with DIP switches.
   (Phase reversal, phase loss, time-current characteristic,
    G,F trip time)

Dip switch selection guide

How to set up

1. CURRENT :
     Definite Time(Function SW#3 OFF)  - Set the rated motor
     current 110~115% of running current after motor run-up
     Inverse Time(Function SW#3 ON) - 100% of rated motor
     current or actual load current is recommended.
2. D-TIME : Set the expected run-up time of motor by
   "D-TIME" potentiometer.
3. O-TIME :
   Definite-Time - Set the desired trip delay time.
   Inverse Time - Set the trip delay time according to
   Time-Current characteristics
4. GROUND:
    Set desired ground fault trip current and set the trip
    time with DIP SW. #4.

Time-current characteristics

Time

                          Current(Multiples of Setting)
     These curves are applied to more then 110% of current setting.

Dimension

Typical wiring diagram

Speification,Test and reset

Protection and indication